Experimental analysis of the air handling unit capable of modulation control based on CO2 content in the classroom
Yazarlar (2)
Öğr. Gör. Murat Korkmaz Hacettepe Üniversitesi, Türkiye
Doç. Dr. Metin KAYA Karabük Üniversitesi, Türkiye
Makale Türü Açık Erişim Özgün Makale (SSCI, AHCI, SCI, SCI-Exp dergilerinde yayınlanan tam makale)
Dergi Adı Heat Transfer Research (Q2)
Dergi ISSN 1064-2285 Dergi Bilgileri (2020)
Dergi Tarandığı Indeksler SCI
Makale Dili İngilizce Basım Tarihi 10-2020
Kabul Tarihi Yayınlanma Tarihi 01-01-2020
Cilt / Sayı / Sayfa 51 / 17 / 1517–1529 DOI 10.1615/HEATTRANSRES.2020035682
Makale Linki http://dl.begellhouse.com/journals/46784ef93dddff27,forthcoming,35682.html
UAK Araştırma Alanları
Tesisat Teknolojisi
Özet
People spend most of their lives indoors today. Therefore, the importance of indoor air quality increases with each passing day, particularly, when the current quality of life expectations is taken into consideration. One of the factors affecting indoor air quality is the amount of CO 2 in the air. In this study, by using an air-handling unit (AHU) with plate heat recovery, the correlation of CO 2 concentration variations based on the number of students present in a classroom of the university was evaluated. Also, alterations in the energy consumption, depending on the variable mixing unit ratios of AHU, were monitored. In the measurements, the measured CO 2 concentration was at its highest level (1350 ppm) while the AHU was not active and 70 students were in the classroom. The CO 2 concentration was 1087 ppm when 50 students were in the classroom. When the AHU was operated with 100% fresh air, the CO 2 …
Anahtar Kelimeler
Air-conditioning unit | Carbon dioxide | Energy conservation | Plate heat recovery
BM Sürdürülebilir Kalkınma Amaçları
Atıf Sayıları
Web of Science 7
Scopus 7
Google Scholar 7
Experimental analysis of the air handling unit capable of modulation control based on CO2 content in the classroom